Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827
Not available for purchase
Not available for purchase

Switch Amplifier KFD2-SRT-Ex1

KFD2-SRT-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Relay output and active transistor output
  • Line fault detection (LFD)
  • Reversible mode of operation

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-SRT-Ex1

General specifications
Signal typeDigital Input
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 35 V DC
Ripple≤ 10 %
Rated current30 mA
Power dissipation0.7 W
Input
Connectionterminals 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Output
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10
Output Isignal ; relay
Output IIsignal ; electronically active
Contact loading253 V AC/ 2 A / cos φ > 0.7 ; 40 V DC/ 2 A resistive load
Mechanical life10 7 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
External supply (loop)
Signal level1-signal: (L+) -3.5 V (current 100 mA, short-circuit protected) / 0-signal: switched off (off-state current ≤ 10 µA)
Transfer characteristics
Redundancy
Output I≤ 25 Hz
Output II≤ 1 kHz
Galvanic isolation
Output/power supplybasic insulation according to IEC 61140, rated insulation voltage 50 Veff
Output/Outputbasic insulation according to IEC 61140, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Low voltage
Directive 2006/95/ECEN 50178:1997
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Height107 mm
Width20 mm
Length115 mm
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2082 , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
InputEEx ia IIC
Voltage12.7 V
Current20 mA
Power62 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output
Contact loading253 V AC/4 A/cos φ ≥ 0.7; 40 V DC/0.5 A resistive load
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Input/power supplysafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 50014, EN 50020
International approvals
FM approval
Control drawing116-0035
CSA approval
Control drawing116-0047
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SRT-Ex1

Product Documentation: KFD2-SRT-Ex1

Language Selection:
ManualsLanguageFile TypeFile Size
ManualENGPDF3685 KB

Design / Simulation: KFD2-SRT-Ex1

Language Selection:
CADLanguageFile TypeFile Size
CAD 2-D / CAD 2-DALLZIP450 KB
CAD 3-D / CAD 3-DALLSTP105 KB
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ57 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.