General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Supply | ||
Rated voltage | 19.2 ... 35 V DC | |
Rated current | 1.46 ... 0.77 A | |
Power dissipation | typ. 6.7 W | |
Fieldbus connection | ||
Number of segments | ||
Simplex | 2 | |
Rated voltage | 25 ... 28 V | |
Rated current | 360 ... 10 mA | |
Short-circuit current | typ. 400 mA | |
PROFIBUS DP | ||
Connection | 9-pin Sub-D socket | |
Protocol | PROFIBUS DP/DP V1 | |
Terminating resistor | 100 Ω integrated | |
Indicators/operating means | ||
LED ERR | red flashing: overload error at output | |
LED Seg 1...2 | red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error | |
LED PWR | Power LED: green if Uout > 25 V | |
LED DP/ERR | red 2 Hz flashing: DP error ; red: Hardware error | |
Galvanic isolation | ||
CH/PROFIBUS DP | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
PROFIBUS DP/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
CH/CH | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Standard conformity | ||
Galvanic isolation | IEC 62103 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 0.9 kg | |
Dimensions | ||
Height | see dimensions | |
Width | see dimensions | |
Depth | see dimensions | |
Mounting | DIN rail, system M36 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242610 |
ETIM 9.0 | EC001600 |
ETIM 8.0 | EC001600 |
ETIM 7.0 | EC001600 |
ETIM 6.0 | EC001600 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121004 |
The FieldConnex ® PROFIBUS Compact Power Hub is a modular fieldbus power supply. The power supply consists of 1 Motherboard as mounting base and wiring interface, 2 Power Modules - 1 per segment, and 1 gateway module for connection to PROFIBUS DP.
Communication is transparent between DP and PA: The gateway Segment Coupler makes each PA device appear as if it was connected to DP. This includes cyclic/acyclic data exchange and transmission speed. Segment design is clear and easy to understand without subnetworks. The PROFIBUS Power Hub Gateway Module itself is configuration-free – all reducing engineering work.
Availability and a long service life are achieved through: only 1 passive impedance filter per segment, optimized design for low-power dissipation, high-availability fieldbus termination, and plug-in connectors with retaining screws.
Datasheet | File Type | File Size |
---|---|---|
Datasheet KT-MB-GTB-2PS | 707 KB | |
Datenblatt KT-MB-GTB-2PS | 706 KB |
CAD | File Type | File Size |
---|---|---|
CAD 2-D / CAD 2-D | ZIP | 881 KB |
Certificates | File Type | File Size |
---|---|---|
DNV Marine | 100 KB |
Software Tools | File Type | File Size |
---|---|---|
GSD converter for transparent gateways / GSD-Konverter für transparente Gateways | ZIP | 793 KB |
Connect process variables from the instrument and their NAMUR diagnostics directly to your control system via CFC function blocks of the Siemens Advanced Process Library. This conveniently automates the entire engineering process via the PROFINET driver library. Find all information in this PDF flyer.