Serviceline Information

Phone: 330-486-0002
Fax: 330-963-5827


  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • 2- or 3-wire Pt100 RTD input
  • Output 4 mA ... 20 mA, temperature linearization selectable
  • DIP switch selectable ranges
  • Sensor breakage detection

Download the complete datasheet as a PDF


Datasheet excerpt: Technical data of KFD0-TR-Ex1

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power loss0.4 W
Input
Connectionterminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection
Lead resistancemax. 100 Ω per lead
Measuring currentapprox. 1 mA
Output
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to ≤ 35 mA
Fault signalupscaling ≥ 22 mA (limited to 35 mA)
Transfer characteristics
Measurement rangespan without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable
zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable
Rise time250 ms
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Data for application in connection with Ex-areas
EC-Type Examination CertificateZELM 00 ATEX 0036 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC
Statement of conformityTÜV 01 ATEX 1777X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA II T4
Directive conformity
Directive 94/9/ECEN 50014, EN 50020 , EN 60079-0:2006, EN 60079-15:2005
International approvals
CSA approval
Control drawing116-0132

Documents: KFD0-TR-Ex1

Instructions, short instructions, safety informationLanguageFile TypeFile Size
System Description Isolated Barriers K-systemENGPDF760 KB
Description du Système pour Barrières Isolées de Système KFRAPDF759 KB
Systembeschreibung Trennbarrieren K-SystemGERPDF745 KB
Systembeschreibung Trennbarrieren K-System/System Description Isolated Barriers K-systemRUSPDF4107 KB

CAD+CAE: KFD0-TR-Ex1

CADFile TypeFile Size
ePLAN-Makros K-System-Geräte (EMA)/ePLAN macros K-System devices (EMA)ZIP17983 KB
Prolist
Prolist Gerätespezifikation/Prolist device specificationXML28 KB

Approvals+Certificates: KFD0-TR-Ex1

CertificatesCertificate No.File TypeFile Size
Canada CSACoC 1029981 CPDF115 KB
Europe TUV Nord ATEX Category 3TÜV 01 ATEX 1777XPDF767 KB
Europe ZELM ATEX Category (1) GDZELM 00 ATEX 0036PDF442 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 06.0004LINK---
Europe Pepperl+Fuchs 94/9/EC - 2004/108/EC Declaration of ConformityPF 08 CERT 1263PDF370 KB
Belarus11-1-019-2013PDF1639 KB
China NEPSIGYJ 091354PDF1374 KB
Russia Belarus EAC Kazakhstan NANIO "CCVE"TC RU C-IT.GB05.B.00718PDF2731 KB
Control drawings
Control Drawing CSA/Controö Drawing CSA   PDF54 KB